datasheets.com EBN.com EDN.com EETimes.com Embedded.com PlanetAnalog.com TechOnline.com  
Events
UBM Tech
UBM Tech

Design Article

Power Tip 35: Minimize transformer interwinding capacitance effects

Robert Kollman, Texas Instruments

5/9/2011 11:36 AM EDT

(Editor's note: to see a linked list of all entries in the Power Tip series, click here.)

Have you ever designed a low-power flyback converter with a high turns ratio? If so, you probably encountered problems with interwinding capacitance. In this Power Tip, we take a look at techniques to reduce the capacitance effects that allow higher frequency operation.

Figure 1 illustrates a circuit that is indicative of the problem. In this transformer, we started with a high turns ratio (40:1) between the secondary and the primary windings.


Figure 1: Interwinding capacitance is problematic with
high transformer-turn ratio..

(Click on image to enlarge)


The transformer has distributed capacitance from the secondary winding-to-ground. The high-voltage switching on the secondary causes current to flow in this capacitance, which is reflected back to the primary. The effective capacitance seen on the primary is the secondary distributed capacitance multiplied by the turns ratio squared.

For instance, 20 pF of distributed capacitance is multiplied by 1600. This appears as 32 nF of capacitance on the primary and generates significant loss. At 100 kHz and 12 volt input, for example, the loss attributed to this capacitance is equal to almost 1 watt in this 4 watt power supply. This capacitance slows the drain voltage as the power FET turns off, robbing you of duty factor. It can also cause false triggering of current limits when the MOSFET turns on.

The secret to reducing current that flows through the capacitance is to minimize the transformer-turns ratio and minimize the voltage across it. There are a number of ways to minimize the voltage. Typically, in these high-voltage circuits, the windings are wound in layers. With two layers, when the end and start are on the same side of the bobbin, the first and last turns have the full winding voltage between them.

One technique used to reduce the gradient between the turns is called bank winding. The wires are wound as shown in Figure 2. This method can significantly reduce the capacitance by limiting the voltages between the adjacent windings. Winding in sections with a split bobbin is an extension of this method.

 


Figure 2: Bank winding reduces effective capacitance.


If the transformer capacitance is still an issue, there are some circuit tricks that you can play. Figure 3 shows an example.


Figure 3: Splitting secondary can halve distributed capacitance..
(Click on image to enlarge)

In this design we have split the secondary windings so that they provide half the voltage of the secondaries shown in Figure 1, but we have connected two of them in series for each output. The average AC voltage on the lower-voltage winding remains the same, while the average AC voltage on the higher winding is reduced by 66 percent. This method reduces the effective transformer capacitance by about half, and can be extended to more sections for even higher voltages.

To summarize, interwinding capacitance can be a problem where large transformer-turns ratios are involved, particularly with low-power converters where losses can be a significant percentage of the load power. The secret to a low-capacitance transformer design is to minimize the turns ratio and to minimize the voltage across adjacent windings.

This can be accomplished by bank, or section windings. You can also split the windings and add rectifiers and filters to further reduce the capacitance. The effective capacitance will be reduced by the number of sections. For instance, four sections reduce capacitance by a factor of four.

Please join us next month when we will discuss the efficiency implications of high-voltage LED’s on the lighting market. For more information about this and other power solutions, visit: www.ti.com/power-ca.

About the author
Robert Kollman is a Senior Applications Manager and Distinguished Member of Technical Staff at Texas Instruments. He has more than 30 years of experience in the power electronics business and has designed magnetics for power electronics ranging from sub-watt to sub-megawatt with operating frequencies into the megahertz range. Robert earned a BSEE from Texas A&M University, and a MSEE from Southern Methodist University.




Robotics Developer

5/10/2011 11:54 AM EDT

The 1 watt waste for a 4W supply is amazing. Thanks for a good basic article with enough technical information to be useful. This will help in the decision process for the next set of power supplies we select.

Sign in to Reply



Etmax

5/11/2011 3:48 AM EDT

Excellent, thanks for the insight

Sign in to Reply



legg

5/12/2011 8:35 AM EDT

Turns ratio reflected impedance to the primary is increased, not reduced, by the turns ratio. This includes capacitive reactance.

You should pull this article before the misinformation spreads too widely.

RL

Sign in to Reply



legg

5/12/2011 8:51 AM EDT

Sorry about that. Didn't see the low voltage input, before posting the previous comment.

RL

Sign in to Reply



Hemanth SP

5/12/2011 11:16 AM EDT

It is a good article for the applications where the voltage is being boosted-up.
Utilizing this paracitic would be even greatful theme.

Sign in to Reply



Winfield Hill

5/14/2011 11:26 AM EDT

Robert, nice article (and the tps61175 is a nice chip!).

What can you tell us about the PA3392NL transformer? Google doesn't seem to reveal anything about that p/n.

Sign in to Reply



Please sign in to post comment

Navigate to related information

Datasheets.com Parts Search

185 million searchable parts
(please enter a part number or hit search to begin)